本文主要研究内容

作者孟庆龙,王文强,郭雪丽,常赛南,谷雅秀(2019)在《变流量空调水系统稳定性的定量评价》一文中研究指出:以一次泵变流量水系统为研究对象,实验研究了无压差控制和定压差控制下变流量空调水系统的水力稳定性.建立了相应的TRNSYS仿真模型,仿真研究了变压差控制下水系统的水力稳定性.结果表明:对于提高系统水力稳定性和节能效益,变压差控制策略效果显著.变压差控制下管网的水力失调系数为0.072,较无压差控制时减小了0.442;关闭任一支路阀门,变压差控制下冷冻水泵节能可达到27.1%.

Abstract

yi yi ci beng bian liu liang shui ji tong wei yan jiu dui xiang ,shi yan yan jiu le mo ya cha kong zhi he ding ya cha kong zhi xia bian liu liang kong diao shui ji tong de shui li wen ding xing .jian li le xiang ying de TRNSYSfang zhen mo xing ,fang zhen yan jiu le bian ya cha kong zhi xia shui ji tong de shui li wen ding xing .jie guo biao ming :dui yu di gao ji tong shui li wen ding xing he jie neng xiao yi ,bian ya cha kong zhi ce lve xiao guo xian zhe .bian ya cha kong zhi xia guan wang de shui li shi diao ji shu wei 0.072,jiao mo ya cha kong zhi shi jian xiao le 0.442;guan bi ren yi zhi lu fa men ,bian ya cha kong zhi xia leng dong shui beng jie neng ke da dao 27.1%.

论文参考文献

  • [1].浅谈供暖空调水系统效率优化策略[J]. 周谨.  价值工程.2018(21)
  • [2].空调水系统管路间耦合特性的分析及试验研究[J]. 李彬,肖勇全,马秀力.  节能.2005(03)
  • [3].供热空调水系统的稳定性分析[J]. 秦绪忠,江亿.  暖通空调.2002(01)
  • [4].重庆某综合楼空调水系统控制策略优化[J]. 廖袖锋,陈明琪,罗天,李腾飞.  建设科技.2016(16)
  • [5].一种新的中央空调水系统节能装备技术与工程应用[J]. 黎小华,闫军威,朱冬生,左政.  化工装备技术.2006(02)
  • [6].空调水系统变流量节能控制分析[J]. 何湘勇.  暖通空调.2007(01)
  • [7].单式磊空调水系统中旁通阀及水泵的选择[J]. 屈国伦.  暖通空调.1995(05)
  • [8].试论空调水系统中阀门的选用[J]. 钟辉.  时代农机.2018(06)
  • [9].浅析空调水系统管道冲洗[J]. 范旭红.  四川水泥.2016(12)
  • [10].中央空调水系统常见问题的分析与解决方案[J]. 李昊.  价值工程.2017(07)
  • 论文详细介绍

    论文作者分别是来自西安建筑科技大学学报(自然科学版)的孟庆龙,王文强,郭雪丽,常赛南,谷雅秀,发表于刊物西安建筑科技大学学报(自然科学版)2019年03期论文,是一篇关于空调水系统论文,水力稳定性论文,压差控制论文,节能论文,西安建筑科技大学学报(自然科学版)2019年03期论文的文章。本文可供学术参考使用,各位学者可以免费参考阅读下载,文章观点不代表本站观点,资料来自西安建筑科技大学学报(自然科学版)2019年03期论文网站,若本站收录的文献无意侵犯了您的著作版权,请联系我们删除。