本文主要研究内容
作者高朋,刘启明,魏俊辉,刘嘉,张伟东(2019)在《基坑内地埋管换热系统水平集管热干扰模拟分析》一文中研究指出:对基坑内地埋管换热系统的水平供回水集管因紧密排布而引起的热干扰进行研究,采用FLUNET软件对水平集管传热过程进行模拟,并对两种水平集管排布方式的热干扰程度及影响进行分析。研究表明:水平集管采用4根供水管与4根回水管相间排布(方案1)和单根供水管与单根回水管相间排布(方案2)均存在一定的热干扰,方案1排布较优,供回水管间的热干扰较小,夏季工况地埋侧回水温度降低0. 2℃/100 m,地源热泵系统制冷量约增加4%,满足设计需求;而冬季工况地埋侧回水温度降低0. 2℃/100 m,地源热泵系统制热量约降低2. 7%,应考虑采用辅助热源以满足建筑热负荷需求。
Abstract
dui ji keng nei de mai guan huan re ji tong de shui ping gong hui shui ji guan yin jin mi pai bu er yin qi de re gan rao jin hang yan jiu ,cai yong FLUNETruan jian dui shui ping ji guan chuan re guo cheng jin hang mo ni ,bing dui liang chong shui ping ji guan pai bu fang shi de re gan rao cheng du ji ying xiang jin hang fen xi 。yan jiu biao ming :shui ping ji guan cai yong 4gen gong shui guan yu 4gen hui shui guan xiang jian pai bu (fang an 1)he chan gen gong shui guan yu chan gen hui shui guan xiang jian pai bu (fang an 2)jun cun zai yi ding de re gan rao ,fang an 1pai bu jiao you ,gong hui shui guan jian de re gan rao jiao xiao ,xia ji gong kuang de mai ce hui shui wen du jiang di 0. 2℃/100 m,de yuan re beng ji tong zhi leng liang yao zeng jia 4%,man zu she ji xu qiu ;er dong ji gong kuang de mai ce hui shui wen du jiang di 0. 2℃/100 m,de yuan re beng ji tong zhi re liang yao jiang di 2. 7%,ying kao lv cai yong fu zhu re yuan yi man zu jian zhu re fu he xu qiu 。
论文参考文献
论文详细介绍
论文作者分别是来自建筑节能的高朋,刘启明,魏俊辉,刘嘉,张伟东,发表于刊物建筑节能2019年02期论文,是一篇关于基坑论文,地源热泵论文,热干扰论文,水平集管论文,建筑节能2019年02期论文的文章。本文可供学术参考使用,各位学者可以免费参考阅读下载,文章观点不代表本站观点,资料来自建筑节能2019年02期论文网站,若本站收录的文献无意侵犯了您的著作版权,请联系我们删除。
标签:基坑论文; 地源热泵论文; 热干扰论文; 水平集管论文; 建筑节能2019年02期论文;